設有室內消火栓的建筑物,包括設備樓層在內,應在每層設置消火栓。屋頂設有直升機停機坪的建筑物,消火栓應設在停機坪出口或非電氣設備間,距停機坪邊緣的距離不應小于5.0米。
For buildings with indoor fire hydrants, including equipment floors, fire hydrants shall be set on each floor. For buildings with helipad on the roof, the fire hydrant shall be set at the exit of the helipad or non electrical equipment room, and the distance from the edge of the helipad shall not be less than 5.0m.
消防電梯前室應設置室內消火栓,應計入消火栓的使用范圍內。建筑物內消火栓的位置應符合滅火要求,并應符合下列要求:
Indoor fire hydrant shall be set in the front room of fire elevator, which shall be included in the scope of use of fire hydrant. The location of fire hydrant in the building shall meet the fire extinguishing requirements and the following requirements:

室內消火栓應設置在樓梯間及其休息平臺,以及前室、過(guò)道等明顯進(jìn)出、易于滅火的地方??蛷d的消防栓應安裝在樓梯間和休息平臺上。車(chē)庫內消火栓的設置不影響車(chē)輛通行和停車(chē)位的設置,保證消火栓的暢通。
Indoor fire hydrants shall be set in the stairwell and its rest platform, as well as the front room, aisle and other places with obvious access and easy to extinguish the fire. The fire hydrant in the living room shall be installed on the staircase and rest platform. The setting of fire hydrants in the garage will not affect the vehicle traffic and the setting of parking spaces, so as to ensure the smooth flow of fire hydrants.
設置在同一樓梯間和附近不同樓層的消火栓應具有相同的平面位置。儲藏室消火栓應設置在常溫室內或樓梯間。
Fire hydrants set in the same staircase and different floors nearby shall have the same plane position. The fire hydrant in the storage room shall be set in the room or staircase at normal temperature.
室內消火栓的布置應滿(mǎn)足2個(gè)實(shí)心水柱和2個(gè)消防水槍在同一平面上的要求,同時(shí)滿(mǎn)足任何部分的要求,但建筑高度小于等于24.0m,容積小于或等于5000m的多層倉庫,建筑高度小于或等于54m。
The layout of indoor fire hydrants shall meet the requirements of two solid water columns and two fire water guns on the same plane, as well as the requirements of any part. However, for multi-storey warehouses with building height less than or equal to 24.0m and volume less than or equal to 5000m, the building height is less than or equal to 54m.
此外,每個(gè)單元配備一個(gè)疏散樓梯,一個(gè)消防水槍的一個(gè)實(shí)質(zhì)性水柱可以到達任何房間的一部分。
In addition, each unit is equipped with an evacuation staircase, and a substantial water column of a fire water gun can reach part of any room.
那么以上就是有關(guān)消防栓的位置設置相關(guān)要求了,希望各位可以作為參考!更多相關(guān)內容您可以隨時(shí)來(lái)我們網(wǎng)站www.guizhouhuli.net進(jìn)行咨詢(xún)!
So the above is the relevant requirements for the location and setting of fire hydrants. I hope you can use it as a reference! For more information, please feel free to visit our website at www.guizhouhuli.net Com for consultation!