RM新时代投资官网

川消_萃聯(lián)
氣體滅火系統
自動(dòng)噴水滅火系統
當前位置:首頁(yè) > 新聞中心消防閥門(mén)發(fā)生內漏怎么處理?

消防閥門(mén)發(fā)生內漏怎么處理?

來(lái)源:http://www.guizhouhuli.net/ 日期:2022-04-20

消防閥是工業(yè)和建筑管道控制的重要配件。主要產(chǎn)品控制精度高,特別是流量控制。目前,它廣泛應用于工業(yè)控制系統中。在使用過(guò)程中,經(jīng)常會(huì )有各種各樣的問(wèn)題困擾著(zhù)我們
Fire valve is an important accessory for industrial and building pipeline control. The main products have high control accuracy, especially flow control. At present, it is widely used in industrial control system. In the process of use, there are often various problems perplexing us
告訴我們消防閥內部泄漏的原因和處理方法。
Tell us the cause and treatment of internal leakage of fire valve.
從問(wèn)題產(chǎn)生的原因及方案分析,
Analyze the causes and solutions of the problems,
消防器材公司的維修人員在加工或組裝過(guò)程中,受工藝影響,很可能造成電動(dòng)調節閥內部泄漏。此時(shí),主要是由于固定限位開(kāi)關(guān)的動(dòng)作以及控制閥在運行過(guò)程中控制介質(zhì)對控制閥的不斷沖刷和作用方式,導致閥門(mén)無(wú)法關(guān)閉,造成內部泄漏。在這方面,我們主要應該調整限位開(kāi)關(guān)的位置來(lái)這一現象。
In the process of processing or assembly, the maintenance personnel of the fire equipment company are likely to cause internal leakage of the electric control valve due to the influence of the process. At this time, it is mainly due to the action of the fixed limit switch and the continuous scouring and action mode of the control medium on the control valve during the operation of the control valve, which makes the valve unable to close and causes internal leakage. In this regard, we should mainly adjust the position of the limit switch to solve this phenomenon.
川消
的消防閥調試不當導致內部泄漏。由于電控閥的控制部分故障,閥門(mén)的限位開(kāi)關(guān)和過(guò)扭矩開(kāi)關(guān)會(huì )導致密封面磨損或腐蝕,也會(huì )導致內部泄漏。在這方面,我們仍應努力調整限位開(kāi)關(guān)。
Improper commissioning of the fire valve resulted in internal leakage. Due to the failure of the control part of the electric control valve, the limit switch and over torque switch of the valve will cause wear or corrosion of the sealing surface and internal leakage. In this regard, we should still strive to adjust the limit switch.
由于電動(dòng)執行機構調零不準確,閥門(mén)無(wú)法完全關(guān)閉,出現內部泄漏。主要調整方法是手動(dòng)關(guān)閉閥門(mén),或在無(wú)法擰緊后將閥門(mén)轉回半圈,以調整調整極限。
Due to the inaccurate zeroing of the electric actuator, the valve cannot be completely closed and internal leakage occurs. The main adjustment method is to close the valve manually or turn the valve back half a turn after it cannot be tightened to adjust the adjustment limit.
通過(guò)向下推關(guān)閉閥門(mén)。如果執行機構的推力不夠大,閥門(mén)將無(wú)法完全關(guān)閉,并會(huì )發(fā)生內部泄漏。主要方案是更換高推力的執行機構。
Close the valve by pushing down. If the thrust of the actuator is not large enough, the valve will not be fully closed and internal leakage will occur. The main solution is to replace the actuator with high thrust.
上一篇:川消消防栓給水系統會(huì )出現怎樣的故障?
下一篇:火災自動(dòng)報警系統施工中存在的問(wèn)題怎么?

相關(guān)產(chǎn)品 / Related products

RM新时代投资官网
RM新时代手机版 RM新时代赚钱项目 RM新时代新项目-百度知道 RM新时代官方网站|首入球时间 新时代app游戏 rm新世界 RM新时代有限公司 rm新时代足球交易平台 RM新时代新项目-百度知道 rm理财